Home - Sensata Power Controls White Bear   Sensata Technologies Home Page
       

Contact Us

Home
 
Standby Power Systems (SPS)
Environmentally Friendly, Quiet, Reliable, AC Power
Output Voltage (VAC) 120 RMS ± 5%
Output Frequency 60 Hz ± 0.05%
Output Waveform Quasi-sine wave, with waveform stabilizer
Input Voltage (VDC) 22 to 28
Operating Temperature  -40° to 40°C (-40°  to 104°F)
Efficiency Up to 93%

Other Design Features:

  • Thermally-controlled cooling fan
  • Enclosed AC and DC cable connections with strain relief
  • Remote ON/OFF switch hookup
  • LED indications of Inverter Power, Low Input Voltage, Overload, and High Temperature
  • Battery voltage indicator with push-to-test
  • LED indication of Battery Charger On, 100% charge level, 80% charge level, & Timer Complete

Unit Protection:

  • Automatic electronic short circuit/overload protection
  • Automatic high temperature shutdown
  • Output circuit breaker

Battery Protection:

  • Automatic low battery shutdown at 21 volts (with in-rush delay)
24V Input Models 24U15BTXP 24X25BTXP 24X36BTXP
Documentation

Output Power (Watts Continuous) 1,500 2,500 3,600
Output Current (Amps AC) Up to 12 Up to 21 Up to 30
Peak Output (Amps AC) 45 80 108
Input Current (Amps DC) Up to 75 Up to 125 Up to 180
Weight (lbs.) 27 48 57
Dimensions (in.) LxWxH 13¼ x 11 x 6¾

14½ x 11½ x 7¾

BATTERY CHARGER    Totally Correct ®, selectable between wet and sealed lead acid batteries, selectable between small and large battery banks
Output Current (Amps DC)   35 70 70
Input Current (Amps AC)   Up to 15 Up to 25 Up to 26
TRANSFER RELAY  Fail-safe shore power Transfer Relay 
Current Rating (Amps AC) 30
Transfer Time (milliseconds) less than 35 typical
Usage: Any 120 VAC, 60 Hz, product within the inverter’s power rating that does not require a pure sine waveform.
Warranty: Full year parts and factory labor