| Standby
Power Systems (SPS) |
| Environmentally
Friendly, Quiet, Reliable AC Power |
|
|
|
| Output Voltage (VAC) |
120/240 RMS ± 7% |
| Output Frequency |
60 Hz ± 1% |
| Output Waveform |
Quasi-sine wave, with
waveform stabilizer |
| Input Voltage (VDC) |
22 to 28 (model
24/6000) and 44 to 56 (model 48/8000) |
| Operating
Temperature |
-20° to 40°C (0° to 104°F) |
| Efficiency |
Up to 90% |
|
 |
 |
|
Other Design Features:
- Thermally-controlled cooling fan
- Enclosed AC and DC cable connections
- Remote ON/OFF switch hookup
- AC receptacle with circuit breaker
- LED indications of Inverter Power, Low Input
Voltage, Overload, and High Temperature
- AC transfer relay with voltage control
- Battery
Charger is temperature compensated, with regulated voltage and current, and
patented state-of-charge detector circuitry
- LED indication of Battery Charger On, 100%
charge level, 80% charge level, and Timer Complete
- LED indication of battery state-of-charge
|
Unit Protection:
- Automatic short circuit and overload protection
- Automatic over temperature protection
- Output circuit breakers
Battery Protection:
- Automatic low battery shutdown at 21 volts on
model 24/6000 and 42 volts on model 48/8000 (with in-rush delay)
|
|
| Models |
ADI-24/6000B1DTXP |
ADI-48/8000B1DTXP |
| Documentation |
 |
| Output Power (Watts Continuous) |
6,000 |
8,000 |
|
Output Current (Amps AC) |
Up
to 25 (2 circuits) |
Up
to 33 (2 circuits) |
|
Peak Output (Amps AC) |
150 |
200 |
|
Input Current (Amps DC) |
Up
to 300 |
Up
to 200 |
|
Weight (lbs.) |
105 |
140 |
|
Dimensions (in.)
LxWxH |
18 x 20 x 12˝ |
| BATTERY
CHARGER "B1" |
Totally Correct ®, selectable between wet and
sealed lead acid batteries, selectable between small and large battery banks |
|
Output Current (Amps DC) |
Up to 180 |
Up to 80 |
|
Input Current (Amps AC) |
Up to 28 @ 240 VAC |
Up to 30 @ 240 VAC |
| TRANSFER
RELAY "T" |
|
| Current
Rating (Amps AC) |
30 at 240 VAC |
50 at 240 VAC |
| Transfer
Time (milliseconds) |
65 |
65 |
|
Usage: Any 120
or 240 VAC, 60 Hz single phase equipment within the inverters power
rating that does not require a pure sine waveform.
Warranty: Full year parts and factory labor |
| |
|