Home - Sensata Power Controls White Bear   Sensata Technologies Home Page
       

Contact Us

Home
 

Standby Power Systems

Environmentally Friendly, Quiet, Reliable AC Power

Output Voltage (VAC)
  230 ±5%
Output Frequency
  50 Hz ± 0.05%
Output Waveform
  Pure sine wave
Input Voltage (VDC)
  22 to 28
Operating Temperature
  -4° to 40° C (20°  to 104° F)
Derate @ 10% per 5
° C
Efficiency
  Up to 85%



O
ther Design Features:
  • Large case MOSFET technology for increased reliability
  • Digital Signal Controller for improved performance
  • High peak AC output current for starting demanding loads
  • Patented construction and cooling methods
  • Thermally controlled cooling fan
  • Enclosed AC and DC cable connections with strain relief
  • Battery Charger is temperature compensated, with regulated voltage and current, and patented state-ofcharge detector circuitry
  • LED status display and battery voltage indicator



Unit Protection:

  • Automatic short circuit and overload protection Automatic over temperature protection
  • Output circuit breakers

             Battery Protection:

  • Automatic low battery shutdown at 21 VDC (with in-rush delay)
MODEL NUMBER 24UA11BF4NT 24XB22BF4NT 24XE33B1F4NT
Documentation
Output Power (Watts Cont.) 1,100

2,200

3,300

Output Current (Amps AC) Up to 4.8 Up to 9.6 Up to 14.3
Peak Output (Amps AC) 15 30 45
Input Current (Amps DC) Up to 55 Up to 110 Up to 165
Weight (lbs.) 27 48 57
Dimensions (in.) LxWxH 13¼ x 11 x 6¾ 14½ x 13 x 7¾ 16¼ x 15¾ x 7¾
BATTERY CHARGER B B B1
Totally Correct ®, selectable between wet and sealed lead acid batteries, selectable between small and large battery banks 1 AC input circuit for transfer and battery charger 1 AC input circuit for transfer and battery charger 2 AC input circuits, one for transfer and one for battery charger
Output Current (Amps DC) 30 75 85
Input Current (Amps AC) Up to 5 Up to 10 Up to 13
TRANSFER RELAY "T" smart relay with low input voltage disconnect  
Current Rating (Amps AC) 5 10 15
Transfer Time (milliseconds)  less than 40 typical

Usage: Any 220 VAC, 50 Hz single phase equipment within inverter's power rating.
Warranty: Two year parts and factory labor